TS 498 – Turkish Building Wind Load Standard

In Turkey, façade wind pressures are determined with TS 498:2021. The standard specifies formulas, coefficients and safety factors depending on height, orientation and panel type. Key points are summarised below.

1. Basic Wind Pressure Formula

w = Cp × q

where q is the velocity pressure (kN/m²) and Cp the aerodynamic coefficient (positive/negative).

2. Velocity Pressure (q)

q = v² / 1600   (TS 498 §14.3)

v = basic wind speed (m/s). Alternatively, design values may be taken directly from Table 4 of the standard.

3. Typical Cp Coefficients

  • Windward flat façade: Cp ≈ +0.80 (pressure) / –0.80 (suction)
  • Side façade (parallel flow): Cp ≈ –0.50
  • Corner zones / overhangs: safety factors may be increased.

4. Increase for Isolated Elements

For individual panels or frames the velocity pressure is increased by 25 %:

qdesign = 1.25 × q

5. Worked Example

  • Height band: 21–100 m
  • v = 42 m/s → q = 1.10 kN/m² (tabulated)
  • Isolated panel: q = 1.10 × 1.25 = 1.375 kN/m²
  • Cp = 0.80 (windward pressure)
  • w = 0.80 × 1.375 ≈ 1.10 kN/m²

Egemen Çalışkan engineers combine TS 498 with TS EN 1991-1-4 to deliver façade designs compliant with both national and Eurocode requirements.